1600 Summer Street, Stamford
Class A Office Space For Sublease
Features:
- Recently built out Class A space ready for 2010 occupancy
- Subdivision possible
- Easy access to I-95 & Merritt Parkway
- Across from shopping center and walkable to downtown
- 36 miles to midtown Manhattan / 48 minutes to Grand Central Station
Amenities:
- Shuttle service to Stamford Train Station
- New lobby, driveway, entrance canopy
- Full service Euro Café
- Health and fitness center
- Multi-media conference center
- Attended lobby
- Connected garage with ample parking
- Dual power grids and multiple fiber optics
- 5 acre corporate campus

Specifications:
Floor Loads (Live Loads)
First: 110 lbs psf
2nd thru 6th: 50 lbs psf plus 10 lbs psf Partition Allowance
Column Spacing
28’-6” by 42’-9”
Ceiling Heights
Slab to Slab: 13’-0”
Drop Ceiling: 8’-6” to 9’-0”
Wattage by Square Foot
6 Watts psf
Life-Safety Systems
Zoned Fire Alarm, Centrally Monitored, with Smoke/Heat Detectors & Duct Smoke Detectors, Horn/Strobes Located Thru-out Building, ADA Compliant
Bathrooms
Two Men/Two Women Per Floor, All ADA Compliant
Elevators
Office Building: (4) Passenger and (1) Freight Traction Type 3,500-Pound Capacity per Elevator, 300 Feet per Minute
Parking Garage: (2) Passenger
Sprinkler System
Office Building: Wet System with Stand Pipe
Loading Dock: Dry System
Parking Garage: Dry System with Stand Pipe
Parking Garage
740 Parking Spaces. 6 Levels, 2 Underground.
Fully Lighted. Security Cameras at All Levels
HVAC
24-Hour Tenant-Controlled HVAC Available
360-Ton Cooling Tower
(24) Heat Pumps, 18 Tons of Cooling Each
(492) Perimeter Heat Pumps, 1 Ton of Cooling Each,
8 Sectional, 4-Stage Gas Boiler @ 314,000 BTU,
(2) 100-Horsepower Circulating Pumps, Supplemental
HVAC Possible
Electrical Service Dual Power Grid*
Main: 4000 Amp. 277/480 Volt, 3 Phase
Riser (North): 1200 Amp. 277/480 Volt, 3 Phase (HVAC)
1200 Amp. 277/480 Volt, 3 Phase (HVAC)
(Lighting/Receptacle)
Riser (South): 1200 Amp. 277/480 Volt, 3 Phase (HVAC)
1200 Amp. 277/480 Volt, 3 Phase (HVAC)
(Lighting/Receptacle)
*Building is fed by 2 separate feeders with an auto switch over in the event of loss of primary feed.